Theoretical study of the earthquake response of the Paradise cooling tower
Technical Report
·
OSTI ID:7149439
A detailed dynamic analysis, presented in a series of reports, was conducted on the seismic response and structural safety of key subsystems (steam generator, high pressure steam piping, coal handling equipment, cooling tower, chimney) of Unit no. 3 of TVA at Paradise, Kentucky in order to: (1) determine for the key components the natural frequencies below 50 Hz and the corresponding normal modes; (2) determine response of plant to seismic disturbances; (3) verify through full scale tests results obtained in (1) and determine estimates of damping needed in (2); (4) determine potential failure modes of major structural components; and (5) determine a spare parts policy for a power system so that outages due to damage from seismic disturbances are minimal. Analytical and experimental methods are used. In this study, the dynamic behavior of the cooling tower is analyzed, using quadrilateral plate and beam elements oriented arbitrarily in space, following analysis and confirmation of their predictive value. Response to 1940 El Centro earthquake parameters is studied, and assumed viscous damping coefficients are considered. Comprehensive results, based on this response, are given.
- Research Organization:
- Purdue Univ., Lafayette, Ind. (USA). School of Aeronautics and Astronautics
- OSTI ID:
- 7149439
- Report Number(s):
- PB-274816
- Country of Publication:
- United States
- Language:
- English
Similar Records
Theoretical study on earthquake response of a reinforced concrete chimney. [Paradise, KY]
Coal handling equipment. [Paradise, KY]
Simple continuum model for dynamic analysis of complex plane frame structures. [Paradise, KY]
Technical Report
·
Thu Jun 03 00:00:00 EDT 1976
·
OSTI ID:6970325
Coal handling equipment. [Paradise, KY]
Technical Report
·
Thu Jun 03 00:00:00 EDT 1976
·
OSTI ID:6970324
Simple continuum model for dynamic analysis of complex plane frame structures. [Paradise, KY]
Technical Report
·
Thu Jun 03 00:00:00 EDT 1976
·
OSTI ID:6874815
Related Subjects
20 FOSSIL-FUELED POWER PLANTS
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
COOLING TOWERS
DYNAMIC LOADS
EARTHQUAKES
FAILURES
FOSSIL-FUEL POWER PLANTS
GROUND MOTION
KENTUCKY
MOTION
NORTH AMERICA
POWER PLANTS
SEISMIC EFFECTS
SEISMIC EVENTS
SOUTHEAST REGION
STRESS ANALYSIS
THERMAL POWER PLANTS
USA
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
COOLING TOWERS
DYNAMIC LOADS
EARTHQUAKES
FAILURES
FOSSIL-FUEL POWER PLANTS
GROUND MOTION
KENTUCKY
MOTION
NORTH AMERICA
POWER PLANTS
SEISMIC EFFECTS
SEISMIC EVENTS
SOUTHEAST REGION
STRESS ANALYSIS
THERMAL POWER PLANTS
USA