Solar heating feasibility study. Interim report, 1 Jul 1974--1 Jun 1975
Technical Report
·
OSTI ID:7138546
A growing number of buildings are equipped to capture solar energy for space and water heating. Calculations for a local Navy two-story apartment building using available weather and insolation data indicate that during a typical year a solar collector with an area of 1000 square feet, 1/3 the plan area of the building, could supply 173 million Btu, 37% of the heat required, at an annual cost of $9 per million Btu. This could be reduced to $5 per million Btu if the first cost of the collector were reduced from the estimated $8 to $3 per square foot.
- Research Organization:
- Naval Academy, Annapolis, Md. (USA). Environmental Protection Research and Development Team
- OSTI ID:
- 7138546
- Report Number(s):
- AD-A-025465; USNA-EPRD-12A