Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Long-term reliability of amorphous alloy wound core distribution transformers

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.277696· OSTI ID:7115266
;  [1]; ;  [2]; ;  [3]
  1. Tokyo Electric Power Co. (Japan)
  2. Takaoka Electric Manufacturing. Co. Ltd., Tokyo (Japan)
  3. Hitachi Ltd., Tokyo (Japan)
In order to verify long-term reliability of amorphous alloy wound core distribution transformers, accelerated aging tests and field trials used by actual transformers were practiced. As for accelerated aging tests, short-circuit tests were added to imitate mechanical stress in operation on a utility's distribution system. As a result, even after the equivalent of 30 years, which was the normal expected transformer's life, magnetic characteristic was unchanged, so these transformers could be operated. Also, about field trials, two hundred transformers of four kinds were installed on a utility's distribution system to look into no-load characteristics. They were equipped with a mechanism to measure load current, background vibration and lightning surge current, so the influence for magnetic characteristic could be inspected. As a result, remarkable change wasn't seen even after six months.
OSTI ID:
7115266
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 9:1; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Surge characteristics and protection of distribution transformers. Final report
Technical Report · Sat Dec 31 23:00:00 EST 1983 · OSTI ID:5236528

Effects of voltage surges on extruded dielectric cable life project update
Journal Article · Thu Mar 31 23:00:00 EST 1994 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6985737

Reduction in distribution transformer failure rates and nuisance outages using improved lightning protection concepts
Journal Article · Fri Mar 31 23:00:00 EST 1995 · IEEE Transactions on Power Delivery · OSTI ID:64386