Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Insulation coordination for delta connected transformers

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.296256· OSTI ID:7108332
; ;  [1]
  1. American Electric Power Service Corp., Columbus, OH (United States)
It is common practice to install only phase to ground surge arresters for transformer insulation protection against electrical stresses. However, this may not adequately protect the delta connected transformer phase to phase winding insulation. High phase to phase overvoltages at the transformer terminals, due to capacitor switching, have been reported. This paper describes the excessive phase to phase overvoltages that can also occur due to wave propagation and surge transfer through transformers. This paper points out the need for surge arrester arrangements that protect both, phase to phase and phase to ground transformer insulations. Surge arrester arrangements, selection criteria, installation practices, and application considerations are discussed in this paper.
OSTI ID:
7108332
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 9:2; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Wind Power Plant Grounding, Overvoltage Protection, and Insulation Coordination
Conference · Wed Dec 31 23:00:00 EST 2008 · OSTI ID:1040724

Surge protection of high voltage shunt capacitor banks on ac power systems; Survey results and application considerations
Journal Article · Mon Jul 01 00:00:00 EDT 1991 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5726132

Overvoltage protection of shunt-capacitor banks using MOV arresters
Journal Article · Wed Aug 01 00:00:00 EDT 1984 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6063738