Volatile organic compounds measured at a telephone switching center from 5/30/85-12/6/88: A detailed case study
- Bell Communications Research, Red Bank, NJ (United States)
Volatile organic compounds (VOCs) can cause failures in electronic equipment. This paper presents detailed observations from a three year study of VOCs at a telephone switching office in Neenah, Wisconsin. Included are data on matched indoor and outdoor VOC measurements, as well as corresponding data on HVAC fan operation and ventilation rates. The Neenah office has few occupants and hence provides an opportunity to examine factors that influence VOC levels without the complications associated with daily human activities. As reported in other studies, total VOC levels indoors were greater than those outdoors. During normal periods the total VOC levels were inversely proportional to the air exchange rates. The sources with the greatest influence on the VOC levels tended to be those with the greatest surface area. The results demonstrate that low baseline levels of VOCs can be achieved by minimizing VOC sources and providing adequate ventilation. Even during construction and installation of new switching equipment, the VOC levels, although elevated, remained within tolerable limits. Three months after this activity, levels had returned to pre-installation values. Low concentrations of VOCs and low concentrations of airborne particles were not mutually exclusive, nor was it unduly expensive to achieve such low levels.
- OSTI ID:
- 7015416
- Journal Information:
- Journal of the Air and Waste Management Association; (United States), Journal Name: Journal of the Air and Waste Management Association; (United States) Vol. 42:6; ISSN JAWAE; ISSN 1047-3289
- Country of Publication:
- United States
- Language:
- English
Similar Records
Comparison of predicted and derived measures of volatile organic compounds inside four relocatable classrooms due to identified interior finish sources
Model estimates of the contributions of environmental tobacco smoke to volatile organic compound exposures in office buildings
Related Subjects
540120* -- Environment
Atmospheric-- Chemicals Monitoring & Transport-- (1990-)
AC SYSTEMS
AIR POLLUTION
AIR POLLUTION MONITORING
DEVELOPED COUNTRIES
ECOLOGICAL CONCENTRATION
HVAC SYSTEMS
MATTER
MONITORING
NORTH AMERICA
ORGANIC COMPOUNDS
PARTICLES
PARTICULATES
POLLUTION
POWER SYSTEMS
USA
VENTILATION
VOLATILE MATTER