Improved 60 Hz superconducting power transmission cable
The third in a series of 10 m, Nb/sub 3/Sn cables for ac power transmission has been installed in a horizontal, refrigerated cryostat. Like the two previous ones, this coaxial cable has its ends rigidly fixed so that it cannot contract axially on cooldown, and has two layers of superconducting helices and two layers of high purity aluminum helices for stabilization in each conductor. It differs from the previous one in having thicker electrical insulation (7.4 mm vs 3.6 mm), in having increased contact resistance between the superconducting layers to reduce ac loss, and in being driven by an external supply through horizontal, coaxial, vapor-cooled current leads. This is the final short cable prior to construction late this year of a 100 m cable which will be tested with high voltage and high current simultaneously. Results of current tests are presented, including ac loss at various temperatures and recovery from thermally induced quenches.
- Research Organization:
- Brookhaven National Lab., Upton, NY (USA)
- DOE Contract Number:
- AC02-76CH00016
- OSTI ID:
- 6990030
- Report Number(s):
- BNL-28389; CONF-800980-23
- Country of Publication:
- United States
- Language:
- English
Similar Records
10 m Nb3Sn Cable for 60 Hz Power Transmission
Improved technique to measure electronically AC losses in superconducting cables
Related Subjects
24 POWER TRANSMISSION AND DISTRIBUTION
AC LOSSES
ALLOYS
CABLES
CONDUCTOR DEVICES
DATA
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
ENERGY LOSSES
EQUIPMENT
EXPERIMENTAL DATA
INFORMATION
LOSSES
NIOBIUM ALLOYS
NUMERICAL DATA
PERFORMANCE TESTING
POWER TRANSMISSION
SUPERCONDUCTING CABLES
TESTING
TIN ALLOYS