An experimental analysis of DC excitation of transformers by geomagnetically induced currents

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.296304· OSTI ID:6985977
;  [1];  [2];  [3];  [4]
  1. Tokyo Electric Power Co., Inc. (Japan)
  2. Toshiba Corp., Kawasaki (Japan)
  3. Hitachi, Ltd. (Japan)
  4. Mitsubishi Electric Corp., Ako (Japan)

DC excitation of transformers due to geomagnetically induced currents was studied by model experiments. First, differences in the DC excitation phenomenon due to the iron core structure were studied using three typical small-scale models. The results verified that single-phase three-legged cores were most susceptible and three-phase three-legged cores least susceptible to such excitation effects. Secondly, the local heating due to DC excitation was quantitatively assessed using large-scale core form and shell form models with the most susceptible single-phase three-legged cores. The results demonstrated that the maximum temperature rise was approximately 110 C due to the GIC (200 A/3 phases).

OSTI ID:
6985977
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 9:2; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

FEM analysis of DC saturation to assess transformer susceptibility to geomagnetically induced currents
Journal Article · Thu Jul 01 00:00:00 EDT 1993 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6089428

Experimental analysis of a DC bucking motor blocking geomagnetically induced currents
Journal Article · Fri Dec 31 23:00:00 EST 1993 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:7115243

Harmonics generated from a DC biased transformer
Journal Article · Wed Mar 31 23:00:00 EST 1993 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6001847