A 230 KV power factor correction installation taking into account the low voltage filters

Conference ·
OSTI ID:696739
 [1];  [2];  [3];  [4]
  1. ABB Power T and D Co., Raleigh, NC (United States)
  2. Black and Veatch Construction, Inc., Lake Oswego, OR (United States)
  3. ABB HV Capacitors, Saint-Laurent (Canada)
  4. ABB, Quebec (Canada)
Power factor is an important component for utilities in maintaining the overall efficiency of the power delivery. Utilities encourage industrial customers to provide their own power factor correction for low power factor loads. At the end of large capacity transmission lines utilities tend to provide power factor correction through shunt capacitor banks. With increased number of filter banks in low voltage distribution systems for power factor correction and harmonic filtering, installation of high voltage capacitor banks require careful considerations. In this paper, the study results of a practical 105 MVAR, 230 kV capacitor bank is discussed. The effect of the existing 13.8 kV filter on the installation of the high voltage power factor correction capacitors is examined. The frequency domain analysis to evaluate various resonant frequencies are also discussed.
Research Organization:
Illinois Inst. of Tech., Chicago, IL (United States)
OSTI ID:
696739
Report Number(s):
CONF-990410--PROC.-Vol.2
Country of Publication:
United States
Language:
English

Similar Records

69 kV shunt capacitor bank specification considerations
Conference · Tue Dec 31 23:00:00 EST 1991 · Proceedings of the American Power Conference; (United States) · OSTI ID:7308152

Bridge capacitor bank design and operation
Journal Article · Sun Dec 31 23:00:00 EST 1995 · IEEE Transactions on Power Delivery · OSTI ID:218304

Compact capacitor/filter development. Final report
Technical Report · Sat Mar 31 23:00:00 EST 1984 · OSTI ID:7154970