NRC regulatory positions, as stated in Regulatory Guide 1.106, Revision 1, have been identified by the Office for Analysis and Evaluation of Operational Data (AEOD) as potential contributors to valve motor burnout. AEOD is particularly concerned about the allowed policy of bypassing thermal overload devices during normal or accident conditions. Regulatory Guide 1.106 favors compromising the function of thermal overload devices in favor of completing the safety-related action of valves. The purpose of this study was to determine if the guidance contained in Regulatory Guide 1.106 is appropriate and, if not, to recommend the necessary changes. This report describes thermal overload devices commonly used to protect safety-related valve operator motors. The regulatory guidelines stated in Regulatory Guide 1.106 along with the limitations of thermal overload protection are discussed. Supplements and alternatives to thermal overload protection are also described. Findings and conclusions of several AEOD reports are discussed. Information obtained from the standard review plan, standard technical specifications, technical specifications from representative plants, and several papers are cited.

Research Organization:
US Nuclear Regulatory Commission (NRC), Washington, DC (United States). Div. of Engineering
OSTI ID:
6913252
Report Number(s):
NUREG-1296; ON: TI88012943; TRN: 88-027760
Resource Relation:
Other Information: Portions of this document are illegible in microfiche products
Country of Publication:
United States
Language:
English