skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Stability limit of room air temperature of a VAV system

Conference ·
OSTI ID:687596
;  [1]; ; ;  [2]; ;  [3]
  1. Yamatake-Honeywell Co., Ltd., Tokyo (Japan). Building System Div.
  2. Oyama National Coll. of Technology (Japan)
  3. Tonets Corp., Tokyo (Japan). Engineering Project Dept.

To control heating, ventilating, and air-conditioning (HVAC) systems, it has been necessary to accept an analog system controlled mainly by proportional-plus-integral-plus-derivative (PID) action. However, when conventional PID controllers are replaced with new digital controllers by selecting the same PID parameters as before, the control loops have often got into hunting phenomena, which result in undamped oscillations. Unstable control characteristics (such as huntings) are thought to be one of the crucial problems faced by field operators. The PID parameters must be carefully selected to avoid instabilities. In this study, a room space is simulated as a thermal system that is air-conditioned by a variable-air-volume (VAV) control system. A dynamic room model without infiltration or exfiltration, which is directly connected to a simple air-handling unit without an economizer, is developed. To explore the possible existence of huntings, a numerical system model is formulated as a bilinear system with time-delayed feedback, and a parametric analysis of the stability limit is presented. Results are given showing the stability region affected by the selection of control and system parameters. This analysis was conducted to help us tune the PID controllers for optimal HVAC control.

OSTI ID:
687596
Report Number(s):
CONF-980650-; TRN: IM9944%%261
Resource Relation:
Conference: 1998 ASHRAE summer annual meeting, Toronto (Canada), 20 Jun 1998; Other Information: PBD: 1998; Related Information: Is Part Of ASHRAE transactions 1998: Technical and symposium papers. Volume 104, Part 2; PB: 1511 p.
Country of Publication:
United States
Language:
English

Similar Records

A Survey of Multizone Airflow Simulation Software
Conference · Wed Jul 01 00:00:00 EDT 2020 · OSTI ID:687596

Estimating the indoor air quality and energy performance of VAV systems
Journal Article · Wed Jul 01 00:00:00 EDT 1992 · ASHRAE Journal (American Society of Heating, Refrigerating and Air-Conditioning Engineers); (United States) · OSTI ID:687596

Ventilation air, the economy cycle, and VAV
Journal Article · Sat Oct 01 00:00:00 EDT 1994 · Heating, Piping and Air Conditioning; (United States) · OSTI ID:687596