The effects of fixture type and HVAC integration on fluorescent lamp/ballast performance
Conference
·
OSTI ID:6824645
This paper describes the effects of fixture type and lamp compartment air extract characteristics on lamp/ballast performance. A luminaire/plenum/HVAC simulator was used to measure minimum lamp wall temperature inside four fixture types while varying lamp-compartment extract conditions. Experimental data show that the lumen output of the lamp/ballast system varies by 20% and system efficacy by 10%, depending on the type of fixture and lamp-compartment extract technique employed.
- Research Organization:
- Lawrence Berkeley Lab., CA (USA)
- DOE Contract Number:
- AC03-76SF00098
- OSTI ID:
- 6824645
- Report Number(s):
- LBL-21775; CONF-860903-3; ON: DE87009171
- Resource Relation:
- Conference: IEEE-Industry Applications Society annual meeting, Denver, CO, USA, 28 Sep 1986; Other Information: Portions of this document are illegible in microfiche products
- Country of Publication:
- United States
- Language:
- English
Similar Records
Experimental methodology for determining the system performance of fluorescent lamp, ballast, fixture combinations operating under realistic application conditions
Fixture conditions affect lamp performance
Fluorescent fixtures and ballasts
Technical Report
·
Thu Nov 01 00:00:00 EST 1984
·
OSTI ID:6824645
Fixture conditions affect lamp performance
Conference
·
Sat Nov 01 00:00:00 EST 1986
·
OSTI ID:6824645
Fluorescent fixtures and ballasts
Conference
·
Tue May 01 00:00:00 EDT 1984
·
OSTI ID:6824645