The effects of fixture type and HVAC integration on fluorescent lamp/ballast performance
Conference
·
OSTI ID:6824645
This paper describes the effects of fixture type and lamp compartment air extract characteristics on lamp/ballast performance. A luminaire/plenum/HVAC simulator was used to measure minimum lamp wall temperature inside four fixture types while varying lamp-compartment extract conditions. Experimental data show that the lumen output of the lamp/ballast system varies by 20% and system efficacy by 10%, depending on the type of fixture and lamp-compartment extract technique employed.
- Research Organization:
- Lawrence Berkeley Lab., CA (USA)
- DOE Contract Number:
- AC03-76SF00098