Availabilty of corona cage for predicting radio interference generated from HVDC transmission line

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
DOI:https://doi.org/10.1109/61.57986· OSTI ID:6801358
;  [1]
  1. Central Research Inst. of Electric Power Industry, Tokyo (Japan)

This paper describes a prospect that a corona cage is available for predicting radio interference (RI) generated from HVDC transmission lines. This is based on the assumption that the generation quantity of RI is determined by Fmax (the true maximum conductor surface gradient in the presence of space charge), regardless of surrounding electrode arrangement. This assumption has been verified by tests using corona cages and a test line.

OSTI ID:
6801358
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) Vol. 5:3; ISSN 0885-8977; ISSN ITPDE
Country of Publication:
United States
Language:
English