This paper describes the use of the ''Decoupled Method'' (See Part I) for studying and detailing important facilities of the ground system of the Itaipu Generating Complex (13000 MW), including 4 large nearby substations, interconnected by the ACSR ground-wires of several 500kV and 220kV transmission lines. Of permanent importance was the reduction of ground potential obtained by the utilization of lines with ACSR ground-wires on the spans near the substations. This paper also presents the theoretical justification for the ''decoupling technique'' used as the Step No. 4 of the ''Decoupled Method''. It is also shown that the subdivision of the fault current into two components (''self-neutralized'' and ''non-neutralized'' components) together with the concepts of ''virtual circuit'' and ''real circuit'' as used in the method, are powerful analytical tools for the electrical engineers dealing with the design and performance of ground systems.
- OSTI ID:
- 6799122
- Journal Information:
- IEEE Trans. Power Del.; (United States), Journal Name: IEEE Trans. Power Del.; (United States) Vol. 3:4; ISSN ITPDE
- Country of Publication:
- United States
- Language:
- English
Similar Records
''Decoupled method'' for studying large interconnected grounding systems using microcomputers - Part I - Fundamentals
Grounding measurements at the Itaipu generating complex using the ''extended Eleck method''
Dimensioning of nearby substations interconnected ground system
Journal Article
·
Sat Oct 01 00:00:00 EDT 1988
· IEEE Trans. Power Del.; (United States)
·
OSTI ID:6627976
Grounding measurements at the Itaipu generating complex using the ''extended Eleck method''
Journal Article
·
Sat Oct 01 00:00:00 EDT 1988
· IEEE Trans. Power Del.; (United States)
·
OSTI ID:6537994
Dimensioning of nearby substations interconnected ground system
Journal Article
·
Sat Oct 01 00:00:00 EDT 1988
· IEEE Trans. Power Del.; (United States)
·
OSTI ID:6798801
Related Subjects
20 FOSSIL-FUELED POWER PLANTS
200104* -- Fossil-Fueled Power Plants-- Components
99 GENERAL AND MISCELLANEOUS
990220 -- Computers
Computerized Models
& Computer Programs-- (1987-1989)
ANALYTICAL SOLUTION
CABLES
COMPUTERS
CONDUCTOR DEVICES
DECOUPLING
DESIGN
ELECTRIC CABLES
ELECTRIC GENERATORS
ELECTRICAL EQUIPMENT
ELECTRONIC CIRCUITS
ENERGY SYSTEMS
EQUIPMENT
INTERCONNECTED POWER SYSTEMS
MICROELECTRONIC CIRCUITS
MICROPROCESSORS
PERFORMANCE
POWER SYSTEMS
200104* -- Fossil-Fueled Power Plants-- Components
99 GENERAL AND MISCELLANEOUS
990220 -- Computers
Computerized Models
& Computer Programs-- (1987-1989)
ANALYTICAL SOLUTION
CABLES
COMPUTERS
CONDUCTOR DEVICES
DECOUPLING
DESIGN
ELECTRIC CABLES
ELECTRIC GENERATORS
ELECTRICAL EQUIPMENT
ELECTRONIC CIRCUITS
ENERGY SYSTEMS
EQUIPMENT
INTERCONNECTED POWER SYSTEMS
MICROELECTRONIC CIRCUITS
MICROPROCESSORS
PERFORMANCE
POWER SYSTEMS