Investigation of HVDC inverter with series compensation on analogue simulator
- ABB Power Systems, Baden (CH)
- Western Ontario Univ., London, ON (Canada)
- Manitoba HVDC Research Centre, Winnipeg, Manitoba (CA)
HVdc converters connected into weak ac systems require effective application of voltage control devices to ensure satisfactory voltage control and recovery following disturbances. Both an MOV arrangement and a series capacitor were found to be potentially very cost effective solutions in investigations using digital simulation. However, although the series capacitor performed well in controlling temporary overvoltage following HVdc load rejection, satisfactory recovery from faults was difficult to obtain. This paper presents a follow-up study which uses a state-of-the-art analogue simulator to further investigate the performance of the MOV and series capacitor arrangements, especially the fault recovery performance of the latter.
- OSTI ID:
- 6737655
- Journal Information:
- IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) Vol. 5:2; ISSN 0885-8977; ISSN ITPDE
- Country of Publication:
- United States
- Language:
- English
Similar Records
Application of GTO voltage source inverter in a hybrid HVDC link
Advanced HVDC control, Volume 1: Summary report. Final report
Related Subjects
240100* -- Power Systems-- (1990-)
240202 -- Power System Networks
Transmission & Distribution-- DC Systems-- (1990-)
25 ENERGY STORAGE
250400 -- Energy Storage-- Capacitor Banks
99 GENERAL AND MISCELLANEOUS
990200 -- Mathematics & Computers
ANALOG SYSTEMS
CAPACITORS
CHALCOGENIDES
COMPUTERIZED SIMULATION
DC SYSTEMS
ELECTRICAL EQUIPMENT
ELECTRICAL FAULTS
ENERGY SYSTEMS
EQUIPMENT
HVDC SYSTEMS
INVERTERS
OVERVOLTAGE
OXIDES
OXYGEN COMPOUNDS
PERFORMANCE
POWER SYSTEMS
SIMULATION
VOLTAGE REGULATORS