Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Evaluation retest on a hospital-refuse incinerator at Sutter General Hospital, Sacramento, California

Technical Report ·
OSTI ID:6661523
An evaluation test program was conducted to evaluate the effect of incinerator design changes on emissions from the hospital-refuse incinerator. The test was conducted as a part of the California Air Resources Board's program to assess emissions from stationary sources. Daily average oxygen concentrations ranged from 12.1-15.6% and the daily average carbon dioxide concentrations ranged from 4.0-5.5%. Dioxin emissions ranged from 21.0 nanograms per second (ng/sec) for tetrachlorodioxin to 355 ng/sec for the heptachlorodioxin. Furan emission rates ranged from 253 ng/sec for the tetrachlorofuran to 477 ng/sec for the heptachlorofuran. The mass emission rates of hydrochloric acid ranged from 2.6 to 5.8 pounds per hour.
Research Organization:
California State Air Resources Board, Sacramento (USA). Monitoring and Lab. Div.
OSTI ID:
6661523
Report Number(s):
PB-89-103949/XAB; ARB/ML-88-026
Country of Publication:
United States
Language:
English