The transient performance of a commercial residential 3 ton lithium-bromide/water absorption chiller is studied. Emphasis was placed on separating the chiller response from that of the entire test facility so that its transient response could solely be observed and quantified. It was found that the entire system time response and thermal capacitance has a major impact on performance degradation due to transient operation. Isolation of the absorption chiller from system effects showed time to steady state performance to be a linear function of steady state water supply temperatures. These findings summarized in computer algorithms were used to map the integrated performance of a 3 ton absorption chiller.