skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Comparison of the performance of open cycle air conditioners utilizing rotary desiccant dehumidifiers. [Ventilation, recirculation, and Dunkle cycles]

Conference · · Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States)
OSTI ID:6637740

The results of an investigation of open cycle cooling systems using rotary desiccant dehumidifiers are presented. Three systems, the ventilation, recirculation, and Dunkle cycles have been modeled. The performance of these systems coupled with an air-based solar system has been determinded using TRNSYS simulations of system operation in four representative U.S. climates. The system COP, fraction of the total cooling load met by the desiccant system, and fraction of the thermal energy provided by solar energy are compared. An assessment of the effect of climate and system parameters on the relative performance of the three system configurations is made. It is shown that in order to meet residential loads of 7-11 kW with a COP on the order of unity, systems with high effectiveness must be employed. These systems were also found to perform well when operated solely with a solar thermal imput.

Research Organization:
Univ. of Wisconsin, Madison
OSTI ID:
6637740
Report Number(s):
CONF-800604-P2
Journal Information:
Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States), Vol. 3.1; Conference: American section of the International Solar Energy Society conference, Phoenix, AZ, USA, 2 Jun 1980
Country of Publication:
United States
Language:
English