Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

System design report, March 1978. [Water-to-air heat pump; includes engineering drawings]

Technical Report ·
OSTI ID:6637183
A solar space heating demonstration project is reported. It describes an integrated system providing solar energy space heating for a 9982 sq. ft., newly built, one-story building. The building is located at 966 Matlack Street, West Goshen Township, Chester County, Pennsylvania. The office part of the building is heated by solar-assisted water-to-air heat pump units. The storeroom part of the building is heated by an airhandling unit, containing a water-to-air coil. Solar energy is expected to provide 62% of the heating load, with the balance provided by a back-up electric boiler. The system includes 1900 active square feet of flat-plate solar collectors, and a 6000 gallon above-ground storage tank. Freeze protection is provided by a gravity drain-down scheme combined with nitrogen pressurization in a closed circuit.
Research Organization:
Bell Telephone Co. of Pennsylvania, Philadelphia (USA)
OSTI ID:
6637183
Report Number(s):
COO-4048-78-1
Country of Publication:
United States
Language:
English