Residential air-to-air heat exchangers: a study of the ventilation efficiencies of wall- or window-mounted units
Mechanical ventilation systems with air-to-air heat exchangers can be installed into residences to provide energy efficient supplementary ventilation for the purpose of controlling indoor concentrations of contaminants, odors, and moisture. Wall or window-mounted units have become particularly attractive because they are relatively inexpensive and easy to install, however, because they lack an air distribution system, concern has arisen over their ventilation performance. To address this concern, a series of experiments was conducted on two different models of wall- or window-mounted heat exchangers in two multi-room research facilities. The nominal ventilation efficiencies of these units have been determined by measurement of tracer gas decay rates at several indoor locations to be in the range of 0.44 or 0.65. No significant correlations between nominal ventilation efficiency and heat exchanger model or operational strategies were observed. Significantly higher local ventilation efficiencies were noted in the rooms where the heat exchangers were operating. Some preliminary tests indicate that internal leakage between the airstreams contributes significantly to the ventilation inefficiency of these systems.
- Research Organization:
- Lawrence Berkeley Lab., CA (USA)
- DOE Contract Number:
- AC03-76SF00098
- OSTI ID:
- 6623417
- Report Number(s):
- LBL-14358; ON: DE83004752
- Country of Publication:
- United States
- Language:
- English
Similar Records
Ventilation efficiencies of wall- or window-mounted residential air-to-air heat exchangers
Residential air-to-air heat exchangers: a study of the ventilation efficiencies of wall- or window-mounted units
Ventilation efficiencies of wall-or-window-mounted residential air-to-air heat exchangers
Conference
·
Sun May 01 00:00:00 EDT 1983
·
OSTI ID:5784289
Residential air-to-air heat exchangers: a study of the ventilation efficiencies of wall- or window-mounted units
Technical Report
·
Wed Sep 01 00:00:00 EDT 1982
·
OSTI ID:5110157
Ventilation efficiencies of wall-or-window-mounted residential air-to-air heat exchangers
Conference
·
Wed Jun 01 00:00:00 EDT 1983
· ASHRAE Trans.; (United States)
·
OSTI ID:6772316
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320101* -- Energy Conservation
Consumption
& Utilization-- Residential Buildings-- (-1987)
BUILDINGS
DATA
EFFICIENCY
ELEMENTS
EXPERIMENTAL DATA
FLUIDS
FLUORIDES
FLUORINE COMPOUNDS
GASES
HALIDES
HALOGEN COMPOUNDS
HEAT EXCHANGERS
HOUSES
INFORMATION
ISOTOPE APPLICATIONS
LEAKS
NONMETALS
NUMERICAL DATA
PERFORMANCE TESTING
RADON
RARE GASES
RESIDENTIAL BUILDINGS
SULFUR COMPOUNDS
SULFUR FLUORIDES
TESTING
TRACER TECHNIQUES
VENTILATION SYSTEMS
320101* -- Energy Conservation
Consumption
& Utilization-- Residential Buildings-- (-1987)
BUILDINGS
DATA
EFFICIENCY
ELEMENTS
EXPERIMENTAL DATA
FLUIDS
FLUORIDES
FLUORINE COMPOUNDS
GASES
HALIDES
HALOGEN COMPOUNDS
HEAT EXCHANGERS
HOUSES
INFORMATION
ISOTOPE APPLICATIONS
LEAKS
NONMETALS
NUMERICAL DATA
PERFORMANCE TESTING
RADON
RARE GASES
RESIDENTIAL BUILDINGS
SULFUR COMPOUNDS
SULFUR FLUORIDES
TESTING
TRACER TECHNIQUES