Parameters affecting air leakage in east Tennessee homes

Conference ·
OSTI ID:6620361
A major pathway for loss of conditioned air in east Tennessee homes with externally located heating, ventilation, and air-conditioning (HVAC) systems is leakage in the ductwork. The average infiltration rate, as measured by Freon-12 tracer gas dilution, nearly doubles if the central duct fan is operating; duct-fan on and duct-fan off measurements of the rate of air exchange gave mean values of 0.78 and 0.44 h/sup -1/, respectively, in a total of 31 homes. Specific leakage areas measured by the blower-door, pressurization-depressurization technique are affected to a lesser extent by inclusion of the ductwork volume within the total volume of the house that is being pressurized; the average increment in the specific leakage area for a subset of 7 of the study homes is about 15%. For homes that have central HVAC systems, weatherization and energy conservation programs should be cognizant of the seriousness of air and energy losses that can be caused by leaking ductwork. 6 references, 2 tables.