53 kW water cooled solar cooling package for BDP distribution center, Phoenix, Arizona. Final report

Technical Report ·
OSTI ID:6599681
A description is given of the 53 kW water-cooled solar absorption unit installed at the rear of the BDP Arizona Distribution Center, Phoenix, Arizona, for use as the primary means of space comfort cooling. Thermal energy required to run the solar absorption unit is supplied by 133.8 m/sup 2/ of concentrating tracking trough-type Acurex collectors. Surplus solar energy is stored in a 9462 liter insulated steel storage tank. Summaries are given of the performance of the system and the problems encountered. Appendices include: job site photographs, summarized tabulated daily performance data; 3M company trip report; and insolation data from NOAA National Weather Service.