The cost of heat exchanger fouling in the US industries
Conference
·
OSTI ID:6574086
Fouling of heat exchangers costs the US industries hundreds of millions of dollars every year in increased equipment costs, maintenance costs, energy losses and losses in production. The designer of heat exchangers usually allows for fouling by using a fouling factor in the design which results in additional capital cost of the heat exchanger. As fouling deposits build up in a heat exchanger, its performance will start to deteriorate and less energy will be transferred through the unit. A plot is provided that gives the percent decrease in heat flux, for a constant driving temperature difference, as a function of the clean overall heat transfer coefficient and the fouling factor. Another plot gives the increase in surface area due to fouling for the same heat transfer rate and driving temperature difference, as a function of the clean overall heat transfer coefficient and the fouling factor. The overall heat transfer market was divided into four sectors: the chemical, petroleum, electric utility and other industries. The 1982 US sales of all industrial heat exchangers, excepting boilers and automotive radiators, was about 285,000 units amounting to about $1.6 billion. The total heat duty of all the heat exchangers in industrial operation, including electric utilities, was estimated at 11.7 Quads. If this represented the amount of heat transferred through clean heat exchangers, the decrease in energy transferred due to fouling or the cost of fouling in terms of energy lost was estimated at 2.9 Quads annually. The cost of fouling, in providing for additional surface area to compensate for a decrease in heat transfer, was conservatively estimated at $180 million in 1982. 12 refs., 2 figs., 5 tabs.
- Research Organization:
- EG and G Idaho, Inc., Idaho Falls (USA)
- DOE Contract Number:
- AC07-76ID01570
- OSTI ID:
- 6574086
- Report Number(s):
- EGG-M-39187; CONF-880982-3; ON: DE89005179
- Country of Publication:
- United States
- Language:
- English
Similar Records
The impact of heat transfer enhancement techniques on energy savings in the US industry
Critical review of organic fluid fouling
Heat Exchanger Fouling - Prediction, Measurement and Mitigation
Conference
·
Thu Dec 31 23:00:00 EST 1987
·
OSTI ID:6830666
Critical review of organic fluid fouling
Technical Report
·
Wed Nov 30 23:00:00 EST 1988
·
OSTI ID:5058729
Heat Exchanger Fouling - Prediction, Measurement and Mitigation
Conference
·
Tue Sep 12 00:00:00 EDT 1989
·
OSTI ID:6517535
Related Subjects
20 FOSSIL-FUELED POWER PLANTS
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320303 -- Energy Conservation
Consumption
& Utilization-- Industrial & Agricultural Processes-- Equipment & Processes
COMPILED DATA
COST
DATA
EFFICIENCY
ENERGY TRANSFER
FOULING
HEAT EXCHANGERS
HEAT TRANSFER
INDUSTRY
INFORMATION
MAINTENANCE
NUMERICAL DATA
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320303 -- Energy Conservation
Consumption
& Utilization-- Industrial & Agricultural Processes-- Equipment & Processes
COMPILED DATA
COST
DATA
EFFICIENCY
ENERGY TRANSFER
FOULING
HEAT EXCHANGERS
HEAT TRANSFER
INDUSTRY
INFORMATION
MAINTENANCE
NUMERICAL DATA