A Preliminary Report on Fire Protection Research Program Fire Barriers and Fire Retardant Coatings Tests
- Sandia National Lab. (SNL-NM), Albuquerque, NM (United States)
An exposure fire test at Sandia Laboratories showed that the Regulatory Guide 1.75 separation guidelines and IEEE-383 fire retardancy standards for safety cables are not sufficient, in themselves, to protect against such fires. Additional measures have been required by NRC to protect essential safety systems against the effects of fires. Two of these measures are fire barriers or fire-retardant coatings on cabling. The report describes the second phase of a small scale and full scale testing program which has been undertaken to assess the adequacy of coatings. In addition, full scale tests are described using exposure fires to appraise the adequacy of some fire barriers placed between horizontal cable trays. The preliminary results show that all coatings and barriers offer some measure of additional protection. Their relative effectiveness is demonstrated by quantitative information obtained in the donor and donee cable trays. An evaluation of other protective measures will be undertaken in future studies.
- Research Organization:
- Sandia National Laboratories (SNL-NM), Albuquerque, NM (United States)
- Sponsoring Organization:
- USDOE; USNRC
- DOE Contract Number:
- EY-76-C-04-0789
- OSTI ID:
- 6555524
- Report Number(s):
- NUREG/CR--0381; SAND--78-1456
- Country of Publication:
- United States
- Language:
- English
Similar Records
Preliminary report on fire protection research program. Fire retardant coatings tests (December 7, 1977--January 31, 1978)
Fire Protection Research Program at Sandia Laboratories. [BWR; PWR]
Fire Protection Research Program at Sandia National Laboratories
Technical Report
·
Tue Feb 28 23:00:00 EST 1978
·
OSTI ID:7277471
Fire Protection Research Program at Sandia Laboratories. [BWR; PWR]
Conference
·
Mon Dec 31 23:00:00 EST 1979
·
OSTI ID:5424204
Fire Protection Research Program at Sandia National Laboratories
Conference
·
Mon Dec 31 23:00:00 EST 1979
·
OSTI ID:6986230
Related Subjects
22 GENERAL STUDIES OF NUCLEAR REACTORS
220200 -- Nuclear Reactor Technology-- Components & Accessories
220900* -- Nuclear Reactor Technology-- Reactor Safety
CABLES
COATINGS
CONDUCTOR DEVICES
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
EQUIPMENT
FIRE HAZARDS
FIRE PREVENTION
FIRE RESISTANCE
HAZARDS
PERFORMANCE TESTING
POWER REACTORS
PROTECTIVE COATINGS
REACTORS
TESTING
220200 -- Nuclear Reactor Technology-- Components & Accessories
220900* -- Nuclear Reactor Technology-- Reactor Safety
CABLES
COATINGS
CONDUCTOR DEVICES
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
EQUIPMENT
FIRE HAZARDS
FIRE PREVENTION
FIRE RESISTANCE
HAZARDS
PERFORMANCE TESTING
POWER REACTORS
PROTECTIVE COATINGS
REACTORS
TESTING