Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Summary review of building energy-use compilation and analysis (BECA). Part C. Conservation progress in retrofitted commercial buildings

Technical Report ·
OSTI ID:6543068
Data on actual energy use were compiled for 223 retrofitted commercial buildings and analyzed for energy performance and cost-effectiveness. 70% of the buildings were located in the northeastern region of the US. Dominant building types were schools and offices; over 75% of the buildings had floor areas larger than 50,000 ft/sup 2/. Nearly all (95%) of the buildings included operations and maintenance changes as part of the retrofit. The median value of source energy savings for the entire sample was 19% of the pre-retrofit consumption. Nine percent of the retrofits failed to save. The median value of retrofit cost was $0.56/ft/sup 2/. Complete cost data were available for less than 30% of the sample; for them the median value of simple payback time was in the 1 to 2 year range and the median value of cost of conserved site energy was $3.30/MBtu (with first-costs amortized over 5 years at 10% real interest). Also included are a study of the durability of retrofits and a comparison of predicted vs. actual savings.
Research Organization:
Lawrence Berkeley Lab., CA (USA)
DOE Contract Number:
AC03-76SF00098
OSTI ID:
6543068
Report Number(s):
LBL-15375; CONF-820849-18; ON: DE83005999
Country of Publication:
United States
Language:
English