Title: Potential of the zeotropic mixture R-22/R-142b in high-temperature heat pump water heaters with capacity modulation

Conference ·
OSTI ID:653213
;  [1]
  1. Rand Afrikaans Univ., Auckland Park (South Africa)

A high-temperature electrically operated heat pump water heater is evaluated in terms of the viability of employing capacity control using zeotropic refrigerant mixtures. The system coefficient of performance (COP) is improved by introducing capacity control, which offers continuous modulation by varying heat pump capacity to match the load. This is accomplished by using a zeotropic refrigerant mixture and changing the composition (x) of the circulating mixture. The zeotrope R-22/R-142b is selected due to the requirements for a high condensing temperature and a wide capacity range. A comparison is made of the energy-saving potential of the R-22/R-142b mixture in a capacity-controlled heat pump, relative to an R-22 heat pump. Computer simulations show that the capacity-controlled heat pump, operating between compositions of 100% R-22 and 70% R-22, shows a 29.6% improvement in energy conversion when compared with a conventional R-22 heat pump water heater. An advanced heat pump water heater is proposed, which would exploit the advantages of using a zeotropic mixture.

OSTI ID:
653213
Report Number(s):
CONF-980123-; TRN: IM9827%%106
Resource Relation:
Conference: 1998 ASHRAE winter meeting, San Francisco, CA (United States), 17-21 Jan 1998; Other Information: PBD: 1998; Related Information: Is Part Of ASHRAE transactions 1998. Volume 104, Part 1A: Technical papers; PB: 834 p.
Country of Publication:
United States
Language:
English