Environmental assessment of a wood-waste-fired industrial watertube boiler. Volume 2. Data supplement. Final report, March 1981-March 1984

Technical Report ·
OSTI ID:6524502
The two-volume report gives results from field tests of a wood-waste-fired industrial watertube boiler. Two series of tests were performed: one firing dry (11% moisture) wood waste, and the other firing green (34% moisture) wood waste. Emission measurements included: continuous monitoring of flue-gas emissions; source-assessment sampling system (SASS) sampling of the flue-gas with subsequent laboratory analysis of samples to give total flue-gas organics in two boiling-point ranges, compound category information within these ranges, specific quantitation of the semi-volatile organic priority pollutants, and flue gas concentrations of 73 trace elements; Method 5 sampling for particulate; controlled condensation system sampling for SO/sub 2/ and SO/sub 3/; and grab sampling of boiler mechanical collector hopper ash for inorganic and organic composition determinations. Total organic emissions decreased from 60-135 mg/dscm firing dry wood to 2-65 mg/dscm firing green wood, in parallel with corresponding boiler CO emissions.
Research Organization:
Acurex Corp., Mountain View, CA (USA). Environmental Systems Div.
OSTI ID:
6524502
Report Number(s):
PB-87-177531/XAB; TR-82-98/EE-VOL-2
Country of Publication:
United States
Language:
English