A multi-tracer technique for studying rates of ventilation, air distribution patterns, and air exchange efficiencies
Conference
·
OSTI ID:6508922
A multiple tracer system has been utilized within commercial buildings to monitor ventilation rates, air exchange efficiencies, age of air at multiple indoor locations, and the fractions of air at a monitoring point that entered the building through a particular air handler and by infiltration. To label the incoming air, a distinct tracer gas is injected at a constant rate into each mechanically supplied outside-air or supply air stream. Gas chromatographs monitor tracer gas concentrations versus time in the major airstreams of the air handlers. Small ''local samplers'' at various indoor locations are utilized to monitor local ages of air. The standard methods of applying age distribution theory are modified to process the multiple tracer data. The experimental system and methods of data analysis are described, and the results of investigations in an office building when the ventilation systems maximized and minimized the recirculation of indoor air are reviewed. The standard deviation in the age of air measured at different locations within this office building is from 25% to 40% of the mean age. Our measurements did not yield evidence of substantial short-circuiting or displacement flow patterns. 3 refs. 2 tabs.
- Research Organization:
- Lawrence Berkeley Lab., CA (USA)
- DOE Contract Number:
- AC03-76SF00098
- OSTI ID:
- 6508922
- Report Number(s):
- LBL-26437; CONF-881263-1; ON: DE89006655
- Country of Publication:
- United States
- Language:
- English
Similar Records
Commercial building ventilation measurements using multiple tracer gases
Indoor air flow and pollutant removal in a room with desk-top ventilation
Indoor air flow and pollutant removal in a room with desk-top ventilation
Conference
·
Thu Sep 01 00:00:00 EDT 1988
·
OSTI ID:7094802
Indoor air flow and pollutant removal in a room with desk-top ventilation
Conference
·
Wed Mar 31 23:00:00 EST 1993
·
OSTI ID:10162797
Indoor air flow and pollutant removal in a room with desk-top ventilation
Conference
·
Wed Mar 31 23:00:00 EST 1993
·
OSTI ID:7368492
Related Subjects
32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION
320107* -- Energy Conservation
Consumption
& Utilization-- Building Systems-- (1987-)
AEROSOL MONITORING
AIR POLLUTION MONITORING
AIR QUALITY
BUILDINGS
COMMERCIAL BUILDINGS
ENVIRONMENTAL QUALITY
FLOW RATE
ISOTOPE APPLICATIONS
MONITORING
TRACER TECHNIQUES
VENTILATION
320107* -- Energy Conservation
Consumption
& Utilization-- Building Systems-- (1987-)
AEROSOL MONITORING
AIR POLLUTION MONITORING
AIR QUALITY
BUILDINGS
COMMERCIAL BUILDINGS
ENVIRONMENTAL QUALITY
FLOW RATE
ISOTOPE APPLICATIONS
MONITORING
TRACER TECHNIQUES
VENTILATION