Electrical endurance of circuit-breakers is not covered by international standards. Special tests, carried out by EDF (Electricite de France) and ENEL, respectively for HV and MV equipment, are described: they have been defined to represent an equivalent stress level to be borne over 25 years in a modern system. They provide a good compromise between cost and representativeness. A 20 years experience shows that the tests make it possible to satisfactorily check the aspects of dimensioning concerning the reliability and to give the operator a quantified guarantee. They have been an important factor in the advances in electrical reliability of circuit-breakers. The requirements of the tests are now satisfied without particular difficulties and integrated by the manufacturers into their development work.

OSTI ID:
6502971
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 8:1; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Reliability testing of power circuit breakers
Journal Article · Wed Dec 31 23:00:00 EST 1975 · Proc. Am. Power Conf.; (United States) · OSTI ID:5320162

Improved combined-cycle plant protection, reliability, and availability using generator circuit breakers
Conference · Sun Dec 31 23:00:00 EST 1989 · OSTI ID:5876418

Worldwide reliability surveys of high voltage circuit breakers
Journal Article · Mon May 01 00:00:00 EDT 1995 · IEEE Power Engineering Review · OSTI ID:63032