Statistical analysis of unsolicited thermal sensation complaints in commercial buildings
Conference
·
OSTI ID:649422
- Johnson Controls, Milwaukee, WI (United States)
Unsolicited complaints from 23,500 occupants in 690 commercial buildings were examined with regard to absolute and relative frequency of complaints, temperatures at which thermal sensation complaints (too hot or too cold) occurred, and response times and actions. The analysis shows that thermal sensation complaints are the single most common complaint of any type and that they are the overwhelming majority of environmental complaints. The analysis indicates that thermal sensation complaints are mostly the result of poor control performance and HVAC system faults rather than inter-individual differences in preferred temperatures. The analysis also shows that the neutral temperature in summer is greater than in winter, and the difference between summer and winter neutral temperatures is smaller than the difference between the midpoints of the summer and winter ASHRAE comfort zones. On average, women complain that it is cold at a higher temperature than men, and the temperature at which men complain that it is hot is more variable than for women. Analysis of response times and actions provides information that may be useful for designing a dispatching policy, and it also demonstrates that there is potential to reduce the labor cost of HVAC maintenance by 20% by reducing the frequency of thermal sensation complaints.
- OSTI ID:
- 649422
- Report Number(s):
- CONF-980123--
- Country of Publication:
- United States
- Language:
- English
Similar Records
Assessing indoor thermal climate - A critical discussion
Predicting the frequency of hot and cold complaints in buildings
Sick building syndrome, sensation of dryness and thermal comfort in relation to room temperature in an office building: Need for individual control of temperature
Journal Article
·
Sat Dec 31 23:00:00 EST 1988
· Environment International; (USA)
·
OSTI ID:6656909
Predicting the frequency of hot and cold complaints in buildings
Conference
·
Wed Jul 01 00:00:00 EDT 1998
·
OSTI ID:20006342
Sick building syndrome, sensation of dryness and thermal comfort in relation to room temperature in an office building: Need for individual control of temperature
Journal Article
·
Sat Dec 31 23:00:00 EST 1988
· Environment International; (USA)
·
OSTI ID:6943066