Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Correction factor to f-chart predictions of active solar fraction in active-passive heating systems

Technical Report ·
OSTI ID:6481818
The extent to which a passive system degrades the performance of an active solar space heating system was investigated, and a correction factor to account for these interactions was developed. The transient system simulation program TRNSYS is used to simulate the hour-by-hour performance of combined active-passive (hybrid) space heating systems in order to compare the active system performance with simplified design method predictions. The TRNSYS simulations were compared to results obtained using the simplified design calculations of the f-Chart method. Comparisons of TRNSYS and f-Chart were used to establish the accuracy of the f-Charts for active systems. A correlation was then developed to correct the monthly loads input into the f-Chart method to account for controller deadbands in both hybrid and active only buildings. A general correction factor was generated to be applied to the f-Chart method to produce more accurate and useful results for hybrid systems.
Research Organization:
Wisconsin Univ., Madison (USA)
OSTI ID:
6481818
Report Number(s):
N-84-26127
Country of Publication:
United States
Language:
English

Similar Records

A correction factor to f-Chart predictions of active solar fraction in active-passive heating systems
Journal Article · Wed Jun 01 00:00:00 EDT 1983 · Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States) · OSTI ID:5122081

Effects of detailed solar-climatology on the accuracy of f-chart
Conference · Wed Dec 31 23:00:00 EST 1980 · Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States) · OSTI ID:5688993

Analysis of hybrid solar systems with active collection and passive distribution