Experimental verification of HVDC test sources requirements for pollution tests
Journal Article
·
· IEEE Transactions on Power Delivery
- CEPEL-Centro de Pesquisas de Energia Eletrica, Rio de Janeiro (Brazil)
- Univ. of Manitoba, Winnipeg (Canada). Dept. of Electric and Computer Engineering
This paper presents the results of tests conducted to verify the effect of the voltage source on the critical flashover voltage of dc insulators under pollution. Tests were performed under 3 pollution levels using voltage sources with different voltage drop x leakage current characteristics. A data acquisition system was used to record all current pulses above a certain pre selected current pulse duration, which made possible a complete analysis of current pulses and voltage drops characteristics. The experimental results show that the present restrictions imposed on the dc voltage sources can probably be relaxed. Also from the experimental data collected it was found that the insulator tested presents a constant impedance x current characteristic. This characteristic can be useful in checking theoretical models for polluted insulator flashover.
- OSTI ID:
- 64437
- Report Number(s):
- CONF-940702--
- Journal Information:
- IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 2 Vol. 10; ISSN 0885-8977; ISSN ITPDE5
- Country of Publication:
- United States
- Language:
- English
Similar Records
Bipolar HVDC transmission system study between +- 600 kV and +- 1200 kV power supply study for insulator pollution tests. Final report
Bipolar hvdc transmission system study: development of controlled cascade rectifier for insulator testing. Final report
Clean fog rapid procedure test of artificially and naturally polluted HVDC porcelain barrel insulators
Technical Report
·
Fri Jul 01 00:00:00 EDT 1977
·
OSTI ID:7299290
Bipolar hvdc transmission system study: development of controlled cascade rectifier for insulator testing. Final report
Technical Report
·
Fri Aug 01 00:00:00 EDT 1980
·
OSTI ID:5165411
Clean fog rapid procedure test of artificially and naturally polluted HVDC porcelain barrel insulators
Journal Article
·
Wed Jul 01 00:00:00 EDT 1992
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:7050533