skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Possibility of high current interruption of vacuum interrupter with low surge contact material: Improved Ag-WC

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.400851· OSTI ID:64387

High-current interruption experiments were carried out on low-surge contact material Ag-WC set in axial magnetic field electrodes. The most influential factors on high-current interruption are the contact material, the axial magnetic field, and the initial opening speed. Though the interruption ability of conventional contact material was limited up to 20 kA, the ability of the improved material rose up to 40 kA in the test using the laboratory model vacuum circuit breaker.

OSTI ID:
64387
Journal Information:
IEEE Transactions on Power Delivery, Vol. 10, Issue 2; Other Information: DN: Paper presented at the IEEE/PES 1992 Winter Meeting, New York, NY, January 26--30, 1992; PBD: Apr 1995