Application of advanced after-laying test to long-distance 275 kV XLPE cable lines

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.400876· OSTI ID:64384
; ;  [1];  [2];  [3];  [4];  [5]
  1. Chubu Electric Power Co., Inc., Nagoya (Japan)
  2. Sumitomo Electric Industries, Ltd., Osaka (Japan)
  3. Furukawa Electric Co., Ltd., Chiba (Japan)
  4. Hitachi Cable, Ltd. (Japan)
  5. Fujikura Ltd., Tokyo (Japan)

Long-distance XLPE cable lines were laid over a distance of 26.9 km (South Route) using the newly established 275 kV XLPE cable technology and in-situ jointing technique. Field ac HV withstanding testing was conducted on these lines as the after-laying test--the first such test for long-distance EHV XLPE cable lines. For this test, small resonance type ac withstanding HV test equipment was developed. A new system was also established for direct and simultaneously measurement of partial discharge over the entire cable length. One latent defect was detected in this test, proving that the test method is extremely effective in confirming the quality of XLPE cable lines.

OSTI ID:
64384
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 2 Vol. 10; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Development of prefabricated joint for 275-kV XLPE cable
Journal Article · Sat Jul 01 00:00:00 EDT 1995 · IEEE Transactions on Power Delivery · OSTI ID:136543

Development of 500-kV XLPE cables and accessories for long distance underground transmission line. Part 3: Electrical properties of 500-kV cables
Journal Article · Sun Mar 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:244793

Development of extruded and molded straight joint for ultra high-voltage XLPE cable
Technical Report · Tue Dec 31 23:00:00 EST 1985 · OSTI ID:6744775