Wastewater treatment plant evaluation, McGuire AFB, New Jersey. Final report, 3-17 November 1986

Technical Report ·
OSTI ID:6361589

The USAFOEHL conducted a survey evaluating the wastewater treatment facility at McGuire AFB, New Jersey. The scope of the survey included the evaluation of: (1) individual-treatment-plant unit processes, (2) influent and effluent sewage quality, (3) treatment plant flow rates, and (4) operational and maintenance practices. Results of the survey showed that the plant was not meeting the 7-day NJPDES effluent standard for Total Phenols, Total Suspended Solids (TSS), and removal efficiency for TSS. Overall, the unit processes of the plant are performing adequately; notwithstanding correctable operation and maintenance difficulties. Recommendation: (1) Perform daily jar testing at the plant. (2) Clean the chlorine contact chamber. (3) Substitute EPA method 604 for EPA method 423 in determining effluent phenol concentration, if possible. (4) Repair the gaps between the clarifier walls and the overflow weirs. (5) Increase the trickling filter recirculation during periods of low influent flow. (6) Consider construction of an aerate wastewater equalization basin.

Research Organization:
Air Force Occupational and Environmental Health Lab., Brooks AFB, TX (USA)
OSTI ID:
6361589
Report Number(s):
AD-A-180202/4/XAB; USAFOEHL-87-038EQ0121CSC
Country of Publication:
United States
Language:
English