Containment Emergency Sump Performance. Technical findings related to Unresolved Safety Issue A-43. Revision 1

Technical Report ·
OSTI ID:6330602
This report summarizes key technical findings related to Unresolved Safety Issue (USI) A-43, Containment Emergency Sump Performance. Both BWRs and PWRs are considered in this report. Emergency core cooling systems require a clean, reliable water source to maintain long-term recirculation following a loss-of-coolant accident (LOCA). PWRs rely on the containment emergency sump to provide such a water supply to residual heat removal pumps and containment spray pumps. BWRs rely on pump suction intakes in the suppression pool or wet well to provide water to residual heat removal and core spray systems. Thus, the technical findings in this report provide information on post-LOCA recirculation. These findings have been derived from extensive experimental studies, generic plant studies, and assessments of sumps used for long-term cooling. Results of hydraulic tests have shown that the potential for air ingestion is less severe than previously hypothesized. The effects of debris blockage on NPSH margin must be dealt with on a plant-specific basis. These findings have been used to develop revisions to Regulatory Guide 1.82 and Standard Review Plan Section 6.2.2 (NUREG-0800).
Research Organization:
Nuclear Regulatory Commission, Washington, DC (USA). Office of Nuclear Reactor Regulation
OSTI ID:
6330602
Report Number(s):
NUREG-0897-Rev.1; ON: TI86900353
Country of Publication:
United States
Language:
English