OSTI ID:6323988

Nuclear power plant fire probabilistic risk assessments (PRAs) usually involve application of a fire growth model to calculate fire growth and the time required to damage critical safety equipment. Attempts to use the fire growth model COMPBRN III resulted in the observation of problems and nonphysical behavior in the code. In this paper the causes of these problems and nonphysical behavior are identified and possible modifications suggested. Incorporation of these modifications into COMPBRN III results in some significant differences in the calculated fire damage times, as well as making the code more physically realistic. 12 refs., 6 figs.

Research Organization:
Sandia National Labs., Albuquerque, NM (USA)
DOE Contract Number:
AC04-76DP00789
OSTI ID:
6323988
Report Number(s):
SAND-88-2160C; CONF-890405-17; ON: DE89005334
Country of Publication:
United States
Language:
English