A performance evaluation of the RPI Passive Solar Visitors Center is presented. Data have been taken and analyzed for January through December 1982. The yearly total energy use is 58.9 MW-h/y (201 MBtu/y), or on a per unit floor area basis, 123 kW-h/m/sup 2/-y (38.7 kBtu/ft/sup 2/-y). These figures agree reasonably well with updated simulation, rather than design simulation, provided realistic values for the interior thermostat set points are used. This energy use represents a 70% reduction in total energy consumption relative to standards of the New York State Energy Conservation Construction Code (construction regulations meant to ensure that energy use in new buildings is below certain values).
Research Organization:
Rensselaer Polytechnic Inst., Troy, NY (USA). Dept. of Mechanical Engineering