Title: Study of fast synchronous-reclosing method for parallel AC line fault in AC/DC power transmission system

Journal Article · · IEEE Trans. Power Appar. Syst.; (United States)

In the AC/DC parallel system, AC power system is separated into two areas by the parallel AC line trip. As a result, it is necessary to recover from asynchronous operation. A method to close tripped AC line, ''Fast synchronous-reclosing method'', is proposed here. This paper consists of two parts: (1) Calculation of the frequency difference limit between the two areas. Energy function is formulated on the condition that fast synchronous-reclosing can be completed satisfactorily. (2) Confirmation of the performance of the fast synchronousreclosing method in the AC/DC parallel line and frequency control before synchronous-reclosing and damping control of the power swing after reclosing, which were studied using an AC/DC simulator.