Measurement of harmonic currents and evaluation of the dc filter performance of the New England - Hydro-Quebec Phase I HVDC Project
Journal Article
·
· IEEE Trans. Power Del.; (United States)
Measurements of harmonic currents in the New England-Hydro-Quebec Phase I HVDC Project de transmission line are presented in this paper. Measurements were conducted to determine the cause of increased telephone interference and to evaluate the dc filter performance. The measurements revealed unexpected high levels of 3-pulse harmonic currents in the dc pole conductors. The cause is attributed to imbalances within the 6-pulse bridges caused by the converter transformer and valve stray capacitances to ground. The conventional model of the converter power circuit used as the basis for the dc filter design does not reproduce the measured 3-pulse harmonics. Modification to this model is required to account for the effect of the converter transformer and valve stray capacitances to ground.
- Research Organization:
- Ebasco Services Inc., New York, NY (US); New England Power Service Co., Westborough, MA (US)
- OSTI ID:
- 6183432
- Journal Information:
- IEEE Trans. Power Del.; (United States), Journal Name: IEEE Trans. Power Del.; (United States) Vol. 4:1; ISSN ITPDE
- Country of Publication:
- United States
- Language:
- English
Similar Records
AC/DC harmonic interactions in the presence of GIC for the Quebec-New England Phase 2 HVDC transmission. [Geomagnetically Induced Current]
A three-pulse model of d. c. side harmonic flow in HVDC systems
Analysis of dc harmonics using the three-pulse model for the intermountain power project HVDC transmission
Journal Article
·
Fri Dec 31 23:00:00 EST 1993
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:7304248
A three-pulse model of d. c. side harmonic flow in HVDC systems
Journal Article
·
Sat Jul 01 00:00:00 EDT 1989
· IEEE Trans. Power Del.; (United States)
·
OSTI ID:5864711
Analysis of dc harmonics using the three-pulse model for the intermountain power project HVDC transmission
Journal Article
·
Fri Mar 31 23:00:00 EST 1989
· IEEE Trans. Power Del.; (United States)
·
OSTI ID:6308390
Related Subjects
13 HYDRO ENERGY
130300 -- Hydro Energy-- Plant Design & Operation
20 FOSSIL-FUELED POWER PLANTS
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
CANADA
CURRENTS
DC SYSTEMS
DESIGN
ELECTRIC CURRENTS
ELECTRIC FILTERS
ENERGY SYSTEMS
FILTERS
HARMONICS
HVDC SYSTEMS
HYDROELECTRIC POWER PLANTS
NORTH AMERICA
OSCILLATIONS
PERFORMANCE TESTING
POWER PLANTS
POWER SYSTEMS
POWER TRANSMISSION LINES
QUEBEC
TESTING
130300 -- Hydro Energy-- Plant Design & Operation
20 FOSSIL-FUELED POWER PLANTS
200101* -- Fossil-Fueled Power Plants-- Cooling & Heat Transfer Equipment & Systems
CANADA
CURRENTS
DC SYSTEMS
DESIGN
ELECTRIC CURRENTS
ELECTRIC FILTERS
ENERGY SYSTEMS
FILTERS
HARMONICS
HVDC SYSTEMS
HYDROELECTRIC POWER PLANTS
NORTH AMERICA
OSCILLATIONS
PERFORMANCE TESTING
POWER PLANTS
POWER SYSTEMS
POWER TRANSMISSION LINES
QUEBEC
TESTING