skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Relay studies: Existing data, current testing and cabinet amplification

Conference ·
OSTI ID:6168628

The seismic fragility of most electrical equipment is governed by the malfunction of relays. This paper discusses the combined study being performed at BNL by evaluating existing fragility test data, conducting a new relay test program and estimating the cabinet amplification at relay locations. Existing test data for relays have been collected and evaluated at BNL. The data base consists of results from a wide variety of test programs - single frequency, single axis, multifrequency, multiaxis tests. For most relays, the non-operating condition controls the chatter fragility limit. In order to characterize the effect of various parameters on the relay seismic capacity, a test program has been initiated at BNL. Selected test specimens will be tested to determine the influence of frequency of vibration, direction of motion, adjustments of relay parts, among others, on the relay capacities. The amplification study involves computing dynamic amplification factors at various device locations in motor control centers and switchgear cabinets. Fragility and high level qualification data have been used for this purpose. This paper includes a summary of the amplification results. 4 refs., 6 figs., 1 tab.

Research Organization:
Brookhaven National Lab., Upton, NY (USA)
DOE Contract Number:
AC02-76CH00016
OSTI ID:
6168628
Report Number(s):
BNL-NUREG-42278; CONF-8810155-46; ON: DE89009520
Resource Relation:
Conference: 16. water reactor safety information meeting, Gaithersburg, MD, USA, 24 Oct 1988; Other Information: Portions of this document are illegible in microfiche products
Country of Publication:
United States
Language: