Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Compliance testing of Eielson Air Force Base Central Heating and Power Plant, coal-fired boiler number 3, Eielson Air Force Base, Alaska. Final report, 12-22 July 1988

Technical Report ·
OSTI ID:6149167
Compliance testing for particulate and visible emissions was conducted on coal-fired boiler No. 3 in the Eielson AFB Central Heat and Power Plant on 12-22 July 88. The survey was conducted as a requirement for renewal of Alaska Department of Environmental Conservation Air Quality Control permit to operate 8331-AA001. Boiler No. 3 was tested at capacities of 100,000 lbs steam/hr and 90,000 lbs steam/hr. Results indicate that boiler No. 3 passed the visible emissions standard, but failed the particulate emission standard.
Research Organization:
Air Force Occupational and Environmental Health Lab., Brooks AFB, TX (USA)
OSTI ID:
6149167
Report Number(s):
AD-A-204505/2/XAB; USAFOEHL-88-149EQ0686MEF
Country of Publication:
United States
Language:
English