Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Transients on transmission systems: data presentation and analysis

Technical Report ·
OSTI ID:6149035

This report contains an analysis of transient data collected with the EPRI Transient Monitoring Laboratories at the Andytown 500-kV and Lauderdale 138-kV Substations on the Florida Power and Light systems. 141 transient events at Andytown and 200 transient events at Lauderdale were recorded. The transient events include results of staged tests and those observed during normal system operation. The report contains a summary of the 341 transient events along with an analysis of the most significant individual events. The events analyzed in this report are grouped according to type into three different categories: lightning, switching, and faults. Of the eight recorded lightning surges to the conductors (i.e., shielding failure or backflash), the two at Lauderdale resulted in faults, and two out of the six at Andytown resulted in faults. In the switching surge analysis presentation, the phase-to-ground overvoltages from all switching events are tabulated. In the fault analysis, voltage and current waveforms for 28 of the 37 fault events were produced. In one particular fault event, a lightning flashover caused a large asymetrical fault current to flow, which caused saturation in the relaying current transformers.

Research Organization:
Westinghouse Electric Corp., Pittsburgh, PA (USA). Research and Development Dept.
OSTI ID:
6149035
Report Number(s):
EPRI-EL-4403; ON: TI86920208
Country of Publication:
United States
Language:
English

Similar Records

Photography helps solve distribution lightning problems
Journal Article · Tue Jun 01 00:00:00 EDT 1993 · IEEE Power Engineering Review (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6020467

Operation of a long-term transient monitoring system in a 138-KV and a 500-KV substation
Journal Article · Wed Aug 01 00:00:00 EDT 1984 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6265728

Summary of transient data obtained from long-term monitoring of a 138-KV and A 500-KV transmission line