Reliability of emergency alternating-current power systems at nuclear power plants: a discussion of NUREG/CR-2989

Journal Article · · Nucl. Saf.; (United States)
OSTI ID:6135249

The reliability of emergency alternating-current power systems typical of most nuclear power plants was estimated by using fault-tree analysis of selected typical designs. The failure probabilities used in the fault trees were calculated from extensive historical data collected from Licensee Event Reports and from operating experience information obtained from nuclear plant licensees. Trends of diesel generator independent failure on demand are included. No one or two improvements can be made at all plants to increase significantly the industry-average emergency alternating-current power system reliability; the most beneficial improvements are varied and plant specific.

Research Organization:
Oak Ridge National Lab., TN
OSTI ID:
6135249
Journal Information:
Nucl. Saf.; (United States), Journal Name: Nucl. Saf.; (United States) Vol. 26:5; ISSN NUSAA
Country of Publication:
United States
Language:
English