Comparison of field performance of a high-efficiency heat pump with and without a desuperheater water heater

Conference · · ASHRAE Trans.; (United States)
OSTI ID:6118519
An air-to-air heat pump run alternately with an electric-resistance water heater and a desuperheater water heater was tested under field conditions. Results from these tests indicate that the desuperheater system has an annual performance factor (measured over a six-month period consisting of three winter and three summer months) 14% better than that of the system using electric resistance water heating. An analytical model predicts a 21% improvement over an entire year with average weather for the desuperheater system. The simple payback period ranges from seven years (for a 21% improvement) to about nine years (for a 14% improvement).
Research Organization:
Oak Ridge National Laboratory
DOE Contract Number:
W-7405-ENG-26
OSTI ID:
6118519
Report Number(s):
CONF-840124-
Conference Information:
Journal Name: ASHRAE Trans.; (United States) Journal Volume: 90:1B
Country of Publication:
United States
Language:
English