skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Energy conservation and solar retrofit analysis of a large office building

Conference · · Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States)
OSTI ID:6113653

During the winter and spring of 1981, a technical energy conservation and solar analysis of the JFK Federal Office Building in Boston was conducted. To reduce the building's energy consumption of a total of nineteen Energy Conservation Measures (ECM's) were analyzed. Among the measures studied were: reduction of ventilation and supply air, central automation controls, programmable lighting, absorption chiller replacement, fenestration modification and heat recovery. The results of the analyse show that implementation of all recommended ECM's would reduce energy consumption by 50% from a raw source Annual Energy Index (AEI) of 33.9 x 10/sup 8/ J/m/sup 2/ (299 MBtu/sf) to 17.2 10/sup 8/ j/m/sup 2/ (152 MBtu/sf). This relates to a savings of approximately $950,000 annually at April 1981 energy costs for a total construction cost of three million dollars.

Research Organization:
R. G. Vanderweil Engineers, Inc., Boston, MA
OSTI ID:
6113653
Report Number(s):
CONF-810925-
Journal Information:
Proc. Annu. Meet. - Am. Sect. Int. Sol. Energy Soc.; (United States), Vol. 6; Conference: 6. national passive solar conference, Portland, OR, USA, 8 Sep 1981
Country of Publication:
United States
Language:
English