High-efficiency heat-pump fan
Conference
·
OSTI ID:6097674
Efforts toward development of a high-efficiency outdoor air mover for an advanced electric heat pump are documented. The design goal was to halve the outdoor air-moving electrical power. The prototype air mover at 850 rpm delivers 3070 scfm through the prototype outdoor unit with a pressure drop through the coil of 0.09 inches of water and consumes 150 watts of electrical power. The overall air-moving efficiency is estimated at about 35 percent compared with 19 percent for the conventionally-applied heat pump fan. Although this air mover will cost twice as much as the conventional heat pump air mover, this premium cost should be recoverable in less than four years through energy savings. The sound rating (SRN) for this air mover is less than 20. Means for improving fan efficiency by 5 percentage points, motor efficiency by 2.5 points, and to further quiet the fan have been identified.
- Research Organization:
- Westinghouse Electric Corp., Pittsburgh, PA (USA). Research and Development Center
- DOE Contract Number:
- W-7405-ENG-26
- OSTI ID:
- 6097674
- Report Number(s):
- CONF-830640-4; ON: DE83014036
- Country of Publication:
- United States
- Language:
- English