Field demonstrations of communication systems for distribution automation, Phase 2. Final report
Technical Report
·
OSTI ID:6066716
The system was designed to provide metering information on the distribution system using bidirectional carrier communications on the distribution lines. A computer at the dispatch control center controlled the system. The computer stored, for later analysis, data collected from the remote terminals. Signal propagation measurements were made at 500 homesites and at 3 primary feeder locations on the distribution system prior to formal system operation. The ability to communicate with each remote device for each attempt averaged over 96 percent, over the six-month operational period. When the distribution circuits were sectionalized to the two alternate configurations, the communication performance remained virtually the same. Functional performance, data collection for all functions, exceeded 99 percent. The project demonstrated that power-line carrier will satisfy communication requirements for automated distribution.
- Research Organization:
- Westinghouse Electric Corp., Raleigh, NC (USA); Detroit Edison Co., MI (USA)
- OSTI ID:
- 6066716
- Report Number(s):
- EPRI-EL-3727; ON: TI85920178
- Country of Publication:
- United States
- Language:
- English
Similar Records
Field demonstrations of communication systems for distribution automation. Final report
Field demonstrations of communication systems for distribution automation
Field demonstrations of communication systems for distribution automation. Volume 1. Program report. Final report
Technical Report
·
Mon Jun 01 00:00:00 EDT 1981
·
OSTI ID:6339241
Field demonstrations of communication systems for distribution automation
Technical Report
·
Tue Jun 01 00:00:00 EDT 1982
·
OSTI ID:5160994
Field demonstrations of communication systems for distribution automation. Volume 1. Program report. Final report
Technical Report
·
Sun Feb 28 23:00:00 EST 1982
·
OSTI ID:5344497