Arc voltage for arcing faults on 25(28)-kV cables and splices

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.252606· OSTI ID:6046008
 [1];  [2]
  1. Inst. de recherche d'Hydro-Quebec, Varennes (Canada)
  2. Hydro-Quebec, Montreal, Quebec (Canada)
Hazards to people and property due to arcing faults on medium-voltage underground cables and splices are related to the arc power dissipated in the environment by the arc. However, if the fault current may be accurately predicted from known circuit parameters, the arc voltage needed to evaluate the arc's power has no analytical expression due to the fact that the arc resistance is non-linear. On the other hand, the arc voltage is also strongly dependent on the inherent physical properties of the faulted equipment, so that in order to establish the arc voltage value and shape developed by different currently used types of equipment, a series of staged tests was performed at IREQ's high-power laboratory and other available data were collected. The results obtained prove that for arc power calculation purposes the arc voltage curve may be considered flat-topped and of constant amplitude specific to the type of faulted equipment.
OSTI ID:
6046008
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 8:3; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Manhole explosions due to arching faults on underground secondary distribution cables in ducts
Journal Article · Wed Jul 01 00:00:00 EDT 1992 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:7050380

Prequalification tests of 345-kV XLPE cable system at IREQ
Conference · Mon Dec 30 23:00:00 EST 1996 · OSTI ID:529594

Successful testing of 345-kV XLPE cables and premolded joints at IREQ
Journal Article · Mon Mar 31 23:00:00 EST 1997 · IEEE Transactions on Power Delivery · OSTI ID:492171