The glove box fire control studies: Interim report

Technical Report ·
DOI:https://doi.org/10.2172/6040166· OSTI ID:6040166
This report describes efforts to develop a safe, practical method to extinguish fires inside contaminated gloveboxes. Oil, trash, and metal fires were set to test various materials and techniques. Dry chemical extinguishers and MgO sand proved more practical than flooding the boxes with either CO/sub 2/ or argon. Gas replacement techniques pressurized the boxes and greatly increased the risk of outside contamination. 5 figs. (TEM)
Research Organization:
General Electric Co., Richland, WA (USA). Hanford Atomic Products Operation
DOE Contract Number:
AC06-76RL01830
OSTI ID:
6040166
Report Number(s):
HW-67074; ON: DE87006395
Country of Publication:
United States
Language:
English